Products
LV Cast Resin Insulated Busway(Aluminum Busway)
LA Series
Inquire Now
Description
Features
Specification
Model | LA04EC | LA08EA | LA12EA | LA16EA | ||
Conductor Marteial | Aluminum | |||||
IP / IK | IP68 / IK 10 | |||||
Frequency (Hz) | 50 / 60 Hz | |||||
Rated Voltage (V) | 1000V | |||||
ln (A) norm | 400 | 630 | 800 | 1000 | 1250 | 1600 |
ln (A) 35/40°C | 500 | 630 | 810 | 1000 | 1375 | 1700 |
Cond mm² | 160 | 240 | 320 | 480 | 720 | 960 |
R20 μΩ/m | 175.0 | 115.0 | 85.6 | 57.0 | 38.5 | 27.8 |
R60 μΩ/m | 202.5 | 133.1 | 99.1 | 66.0 | 44.6 | 32.2 |
R90 μΩ/m | 223.1 | 146.6 | 109.1 | 72.7 | 49.1 | 35.4 |
X μΩ/m | 58.6 | 59.2 | 35.2 | 37.6 | 26.7 | 23.3 |
lcw kA/1Sec | 12 | 18 | 23 | 34 | 40 | 53 |
Ipeak kA | 36 | 36 | 70 | 70 | 84 | 117 |
Ploss 90 W/m | 167.4 | 174.6 | 214.8 | 218 | 278.4 | 307.3 |
Total Weight kg/m | 11.6 | 13.1 | 19.4 | 20.4 | 27.7 | 35.1 |
B x H mm | 104 x 80 | 104 x 120 | 104 x 160 | 104 x 200 |
Model | LA12DA | LA16DA | |
Conductor Marteial | Aluminum | ||
IP / IK | IP68 / IK 10 | ||
Frequency (Hz) | 50 / 60 Hz | ||
Rated Voltage (V) | 1000V | ||
ln (A) norm | 2000 | 2500 | 3150 |
ln (A) 35/40°C | 2380 | 2660 | 3250 |
Cond mm² | 2 x 600 | 2 x 270 | 2 x 960 |
R20 μΩ/m | 23.2 | 19.8 | 14.7 |
R60 μΩ/m | 26.8 | 22.9 | 17 |
R90 μΩ/m | 29.6 | 25.2 | 18.7 |
X μΩ/m | 14.0 | 15.5 | 13.2 |
lcw kA/1Sec | 67 | 80 | 90 |
Ipeak kA | 147 | 176 | 198 |
Ploss 90 W/m | 502.7 | 535.9 | 593.9 |
Total Weight kg/m | 53.9 | 55.4 | 70.2 |
B x H mm | 404 x 160 | 404 x 200 |
* Conductor
1ф3W represents single phase, three wires
3ф3W represents three phases, three wires
3ф4W represents three phases, four wires
G represents grouding phase 100% of rated current
200% N and aluminum grounding conductor optional
* Applicable to DC requirement
* Please refer to the temperture correction coefficient of rated current on page 24 while ambient temoerature exceeds 40°C
* Please contact us directly if the specification is not shown
1ф3W represents single phase, three wires
3ф3W represents three phases, three wires
3ф4W represents three phases, four wires
G represents grouding phase 100% of rated current
200% N and aluminum grounding conductor optional
* Applicable to DC requirement
* Please refer to the temperture correction coefficient of rated current on page 24 while ambient temoerature exceeds 40°C
* Please contact us directly if the specification is not shown
About Us
TAIAN-ECOBAR TECHNOLOGY was formally called TAIAN Electric Co., Ltd.(TECO GROUP). With the drastic increase in the requirement of safety and stability for power distribution, the traditional power cable and metal-enclosure busway can no longer fulfill the requirement from customers. Therefore, the cast resin insulated busway TECOBAR is the best solution in order to meet the requirement. To provide the safest and most reliable power systems to the world is our commitment. Thus, your precious comments and supports are the most incentive to us.
Business Type: None
Main Products
Busway, Busduct, Bus Bar, MV Busway, MV Busduct, LV Busway, LV Busduct, Copper Busway, Copper Bus Bar, Copper Busduct, Aluminum Busduct, Aluminum Busway, Bus Duct, Bus Bars, Cast Resin Busway, Cast Resin Busduct, Cast-Resin Busway, Cast-Resin Busduct